Hanoi-Vietnam: Regulations on inspection and maintenance of gas-based fire extinguishing systems

This content is detailed in Circular 52/2019/TT-BCA promulgating the National Technical Regulation on Fire fighting and prevention apparatus and equipment for storage, delivery port and distribution stations of gas in Vietnam

Inspection  and  maintenance  for  gas  fire  suppression  systems,  Circular  52/2019/TT-BCA

Illustrative image (source: internet)

The contents of inspection and the maintenance cycle for gas-based fire extinguishing systems in Vietnam shall follow the regulations in Table 11 of the National Technical Regulation on "Fire fighting and prevention apparatus and equipment for storage, delivery port and distribution stations of gas - QCVN 01:2019/BCA" issued together with Circular 52/2019/TT-BCA as follows:

Table 11 - Regulations on technical inspection and maintenance for gas-based fire extinguishing systems

 

No.

Content

Inspection and Maintenance Cycle

1

External inspection for mechanical damages, rust, durability of clamps, brackets, and integrity of seal indicators for system equipment:

a) Technical components: pipelines, nozzles, shut-off and control valves, fire extinguishing gas and activation gas cylinders, pressure gauges, and distribution devices for protected objects and areas.

b) Fire alarm signal components: central fire alarm panel, fire alarm detectors, fire alarm and fire extinguishing signal channels, etc.

Weekly

Monthly

Quarterly

2

Inspection of working condition of valves; pressure of pipelines and activation valves of gas cylinders.

Weekly

Monthly

Quarterly

3

Inspection of main power supply and backup power supply, and automatic switch-over from main power to backup power.

Row

week

Row

month

Row

precious

4

Inspection of fire extinguishing gas quantity.

-

Monthly

Quarterly

5

Inspection of the working condition of system components: technological, electrical, and signal parts.

-

Monthly

Quarterly

6

Inspection of system working capability in automatic mode (for automatic systems), remote control, and manual control modes.

-

Monthly

Quarterly

7

Inspection of protective ground resistance.

Weekly

-

-

8

Inspection of insulation resistance of electrical circuits.

Every 3 years

9

Inspection of pipeline strength and tightness.

Every 3.5 years

10

Inspection of safety certificates for pressure equipment as per state regulations.

According to the pressure equipment regulations

The inspection and evaluation of the technical condition of automatic water and foam fire extinguishing systems include checking:

- The condition of fire extinguishing nozzles (in locations with mechanical damage risks, nozzles must be properly protected without affecting the coverage area and fire-induced heat flow).

- The types and sizes of nozzles within each branch pipeline (for each area) must be consistent in type and size.

The technical status evaluation and operational capability of water and foam-based fire extinguishing systems must comply with the standards on "Automatic water-based fire extinguishing systems - General technical requirements and test methods" and "Automatic foam-based fire extinguishing systems - General technical requirements and test methods" and other relevant existing regulations.

Further details may be found in Circular 52/2019/TT-BCA effective from December 18, 2019.

Thu Ba

>> CLICK HERE TO READ THIS ARTICLE IN VIETNAMESE